Seismic qualification of equipment with time histories, sine beats and response spectra.
Requirements
- Objective
- Proof that equipment (e.g. switchgear, control systems) withstands an earthquake without loss of function
- Methods
- Time history, sine beats or sine dwells; assessment via response spectra
- Inputs
- Required response spectrum, damping, duration of the strong-motion part, single- or multi-axis excitation
- Procedure
- Resonance search, then the specified seismic loads; monitor function during and after the test
- Related standards
- IEC 60068-2-57, IEC 60255-21-3 (relays), IEEE 344 (nuclear facilities)
Summary of the key specifications in our own words, without guarantee. The current edition of the standard and your test specification are binding; many values are given there as a choice or as preferred values.