Type tests for protection relays and equipment in severity classes 0 to 2.
Typical parameters
- Parts
- Vibration, shock, seismic
- Classes
- 0, 1, 2
Requirements
- Parts
- -1 vibration (sine), -2 shock and bump, -3 seismic tests
- Test types
- Response test (equipment operating) and endurance/withstand test (not operating)
- Severity classes
- Class 0 no requirement, class 1 for normal service conditions, class 2 for increased requirements (e.g. severe vibration, ships)
- Vibration (part 1), class 2
- Response: 10–150 Hz, 0.075 mm below and 1 g above the crossover frequency; endurance: 2 g, 20 sweep cycles per axis
- Shock (part 2), class 1
- Response 5 g / 11 ms, withstand 15 g / 11 ms, bump 10 g / 16 ms with 1000 bumps per direction
- Note
- A consolidated new edition IEC 60255-21 is in preparation
Summary of the key specifications in our own words, without guarantee. The current edition of the standard and your test specification are binding; many values are given there as a choice or as preferred values.